Westerbeke BTD 10.0 KW 60Hz Installation Manual Page 38

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 37
CONTROL
PANEL
TROUBLESHOOTING
MANUAL
STARTER
DISCONNECT
(TOGGLE
SWITCHES)
NOTE:
The
engine
control system
is
protected by a
20
amp
manual
reset
circuit breaker
located on
the
engine
as
close
as
possible
to
the
power
source.
Problem
Probable
Cause
Verification/Remedy
PREHEAT
depressed,
no
panel
indications
1.
Oil
Pressure
switch.
1.
Check
switches
and/or
battery
connections.
fuel
solenoid,
electric
fuel
pump
and
preheat
solenoid
not
energized.
2.
20
amp
circuit
breaker
tripped.
2.
Reset
breaker.
If
opens
again,
check
preheat
solenoid
circuit
and
run
circuit
for
shorts
to
ground.
START
SWITCH
DEPRESSED.
no
starter
1.
Connection
to
solenoid
faulty.
1.
Check
connection.
engagement.
2.
Faulty
switch
2.
Check
switch
with
ohmmeter.
3.
Faulty
solenoid.
3.
Check
that
12
volts
are
present
at
the
solenoid
connection.
4.
Loose
battery
connections.
4.
Check
battery
connections.
5.
Low
battery.
5.
Check
battery
charge
state.
NO
IGNITION.
cranks.
does
not
start.
1.
Faulty
fueling
system.
1.
Check
for
fuel.
2.
Check
for
air
in
the
fuel
system.
2.
Allow
system
to
bleed.
3.
Faulty
fuel
lift
pump.
3.
Replace
fuel
lift
pump.
NOT
CHARGING
BATTERY
1.
Faulty
alternator
drive.
1.
Check
the
drive
belt
and
its
tension.
Be
sure
the
alternator
turns
freely.
Check
for
loose
connections.
Check
the
output
with
a
voltmeter.
Ensure
12V
are
present
at
the
regulator
tenminal.
BATTERY
RUNS
DOWN
1.
Oil
pressure
SWitch.
1.
Observe
If
the
gauges
and
panel
lights
are
activated
when
the
engine
is
not
running.
Test
the
oil
pressure
switch.
2.
High
resistance
leak
to
grou
nd.
2.
Check
the
wiring.
Insert
sensitive
(0-.25
amp)
meter
in
battery
lines
(Do
NOT
start
engine).
Remove
connections
and
replace
after
short
is
located.
3.
Low
resistance
leak
to
ground.
3.
Check
all
wires
for
temperature
rise
to
locate
the
fault.
4.
Faulty
alternator.
4.
After
a
good
battery
charging.
disconnect
alternator
at
output.
If
leakage
stops.
Remove
alternator
and
bench
test.
Repair
or
replace.
TROUBLESHOOTING
WATER
TEMPERATURE
AND
OIL
PRESSURE
GAUGES
If
the gauge reading is other than what is normally indicated
by the gauge when the instrument panel is energized, the first
step is to check for 12 volts
DC
between the ignition (B+)
and the Negative (B-) terminals
of
the gauge.
Assuming that there is 12 volts as required, leave the instru-
ment panel energized (key switch on) and perform the
following steps:
1.
Disconnect the sender wire at the gauge and see
if
the
gauge reads zero, which is the normal reading for this situa-
tion.
2.
Connect the sender terminal at the gauge to ground and
sec
if
the gauge reads full scale, which is the normal reading
for this situation.
If
both
of
the above gauge tests are positive, the gauge is
undoubtedly
OK
and the problem lies either with the conduc-
tor from the sender to the gauge or with the sender.
If
either
of
the above gauge tests are negative, the gauge is
probably defective and should
be
replaced.
Assuming the gauge is
OK, check the conductor from the
sender to the sender terminal at the gauge for continuity.
Check that the
efIgine block is connected to the ground.
Some starters have isolated ground terminals and
if
the bat-
tery
is connected to the starter (both plus and minus termi-
nals), the ground side
will
not necessarily be connected to the
block.
Engines & Generatots
32
.
Page view 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 63 64

Comments to this Manuals

No comments